120Vac Ceiling Mount Occupancy Sensor Power Pack Supply 24VDC
The MPP-24 supplies low voltage power to occupancy sensors and other control devices, switching line voltage in response to signals from control devices. The power pack is attached to existing junction boxes or mounted into fixture wiring trays.
Low voltage wiring should use at least 22-gauge wire. High voltage connections should use at least 14-gauge. Always check local building codes. After initial wiring is completed, check wiring diagrams to verify the power pack is wired correctly.
Improper wiring can cause damage to the power pack, lighting system, occupancy sensor and other control devices.
MPP-24 | |
Electrical Specifications | |
Voltage | 120/230/277VAC, 50/60Hz |
Load Requirements | |
Incandescent | 20amp @120VAC |
Ballast | 20amp @120/277VAC |
Motor | 1HP@ 120/240VAC |
Output | 150mA @24VDC (with relay connected) |
Low Voltage Input | |
Control ON | 12-24VDC |
Hold ON | 12-24VDC |
Hold OFF | 12-24VDC |
Manual ON(momentary switch required) | 12-24VDC |
Environment Specifications | |
Operating Temperature | 0℃ to +55℃ |
Material Specifications | |
Material | ABS |
Standards & Certifications | |
Certification/Listing | UL |
Applicable Standards | UL 244A, Third Edition, and UL 916 |
Warranty | 2 Year Limited |
Features:
• Self-contained power supply relay system .
• LED indicator of relay operation for easy verification .
• Convert line voltage to low voltage in various lighting control systems .
• Each power pack can be connected with a maximum of six occupancy sensors.
• Easy Installation Essential Component for Ceiling Mounted Occupancy Sensor.
• Certification UL/CUL Listed
Low Voltage Inputs:
Four+12-24VDC input wires are provided to control the load relay.The inputs may be used in combination or individually,depending on the needs of the application .See the Wiring section for wiring information.
Control ON(Blue)- This input is intended for occupancy sensor input.
Applying 12-24 VDC closes the relay.
Remove the voltage and the relay opems if no other input is holding it closed.
Hold ON (Orange)- This input is intended for timer or panel input.
Applying 12-24 VDC closes the relay.
Remove the voltage and the relay opens if no other input is holding it do sed.
It overrides Control ON input.
Refer to figure 4-Typical Wiring From Power Packs to Motion Sensors
Hold OFF(Brown)-This input is used for timer,panel,BAS or load shed input.
Applying 12-24 VDC opens the relay.
Remove the voltage and the relay can accept any other input.
It pverrides Control ON and Hold On inputs.
Installation:
WARNING:TURN POWER OFF AT CIRCUT BREAKER BEFPRE INSTALLATING
1.Make sure power has been turned off at the circuit breaker.
2.Connect wires as shown in the wiring diagram,or as showm in the BI-LEVEL CONTROL section
Installation Notes:
1.Power packs sould be installed in accordance with state,local and national electrical codes and requirnerts.
2.Power packs are designed to attach to exsiting or new electrical endosures with 1/2 inch knockouts
3.Most applications require UL listed,18-22 AWG,3-conductor,Class 2 cable for low voltage wiring. For plenum-approved cables.
4.Rhe MPP-24 is a Class 2 Output power Supply,suitable for parallel interconnection of up to 6 units maximum.This power pack is UL listed for interconnection of power Sources in accordance with National Electric Code.
Q1. What is your terms of payment?
A: We accept TT.
Q2. What is your terms of delivery?
A: FOB, CFR, CIF.
Q3. How about your delivery time?
A: Generally, it will take 7 to 30 days after receiving your advance payment. The specific delivery time depends on the items and the quantity of your order.
Q4. Can you produce according to the samples?
A: Yes, we can produce by your samples or technical drawings. We can build the molds and fixtures.